NUMERICAL ON PSYCHROMETRIC PROCESS | NUMERICAL ON COOLING AND DEHUMIDIFICATION PROCESS

KP Academy
KP Academy
3.4 هزار بار بازدید - پارسال - The following data are given
The following data are given for the space to be air conditioned: Outside air conditions: 40℃ DBT & 50% RH, Inside design conditions: 26℃ DBT & 50% RH, Apparatus Dew Point: 10℃, By-pass factor of the cooling coil: 0.2. The return air from the room is mixed with the outside air before entry to the cooling coil in the ratio 3:1 by mass. If 20m3/min of fresh air is supplied. Find, a) Condition of air leaving the coil, b) Capacity of coil in TR, c) Room sensible heat factor. (MU-May 2016, 14Marks) For Numerical on Adiabatic Mixing of Two Streams refer following video:    • NUMERICAL ON ADIABATIC MIXING OF TWO ...   For more videos please subscribe Channel