Calibrating a Fisher™ 3582 Positioner - Beam Alignment

Fisher Valves & Instruments
Fisher Valves & Instruments
90.5 هزار بار بازدید - 8 سال پیش - Learn about proper calibration and
Learn about proper calibration and beam alignment procedures for the Fisher 3582 pneumatic positioner.

Steps include:
1. Turn the nozzle all the way in and then out four complete turns.
2. Set the input signal to the middle of its range.
3. Move the flapper assembly over the cam and adjust the flapper assembly screw to align the feedback arms.
4. Turn flapper assembly from direct 10 to reverse 10 to align arms using bellows pin and beam pivot pin.

Additional Resources:
– Fisher 3582 Instruction Manual: http://emr.sn/3YH7
– Fisher 3582 Product Bulletin: http://emr.sn/n9PF
– Fisher 3582 Product Webpage: http://emr.sn/Kn5W