DVP PLC Read Pressure from 0 -10vdc analog input , pressure convert psi to bar and ISPSoft

Motive Automation
Motive Automation
219 بار بازدید - 4 ماه پیش - DELTA DVP PLC Analog Read
DELTA DVP PLC Analog Read 0-10vdc and
Display Pressure 0-10bar from 0-10vdc ISPSoft
1 bar = 14.5038 Pound per sqr, inch PSI
0-10vdc Pressure Sensor Analog input Calibration
-------------------------------
All are Proportional Data
Step1) 0-10vdc, 0-10 bar, 10x 14.5 = 145 PSI
Step2) 0-10 = 0-10vdc
      0bar = 0 v
      10 bar/ 145PSI = 10vdc
Step3) 10vdc = Digital RAW data = 2000 Max Raw Data
Step4) Pressure Per/ Digital RAW Val = 10/2000 = 0.005, unit Pressure
Digital RAW Val per/ bar = 2000/10 = 200, Digital Unit
Step5)
Calculation1## Actual Pressure= Digital RAW input or Source Val x 0.005
Calculation2##  Actual Pressure = Digital RAW input or Source Val/200

pressure = RAW Data x .005 Pressure Unit, Float Value
Pressure = RAW Data / 200 Digital unit
We use analog output 0-10vdc for pressure ref.
Ch1 = Connected pressure ref
Ch5 = Analog output 0-10vdc
0 digital val = 0vdc
4000 digital val = 10vdc