IPLV is the AHRI and industry-standard way of measuring the overall average efficiency of a hydronic (chiller) cooling system
IPLV एक हाइड्रोनिक (चिलर) शीतलन प्रणाली की समग्र औसत दक्षता को मापने का AHRI और उद्योग-मानक तरीका है।
IPLV stands for Integrated Part Load Value
IPLV का मतलब इंटीग्रेटेड पार्ट लोड वैल्यू है
Why IPLV  is calculated?
COP and EER are calculated based on full load capacity but in the real world a chiller is hardly always running on full load capacity. So for evaluating  chiller efficiency at different part load condition IPLV  is calculated.  Performance of chiller is measured at different loading condition say 100%, 75%, 50% & 25% and IPLV is calculated
आईपीएलवी की गणना क्यों की जाती है?सीओपी और ईईआर की गणना पूर्ण भार क्षमता के आधार पर की जाती है लेकिन वास्तविक दुनिया में एक चिलर शायद ही हमेशा पूर्ण भार क्षमता पर चल रहा हो। तो अलग-अलग पार्ट लोड कंडीशन में चिलर की दक्षता का मूल्यांकन करने के लिए IPLV की गणना की जाती है। चिलर का प्रदर्शन अलग-अलग लोडिंग कंडीशन में मापा जाता है जैसे 100%, 75%, 50% और 25% और IPLV की गणना की जाती है
IPLV  = 0.01A+0.42B+0.45C+0.12D
Four Data Points Used in IPLV Calculation (EER) / COP
“A” 1% of the time Chiller is running at 100% Capacity
“B” 42% of the time Chiller is running at 75% Capacity
“C” 45% of the time Chiller is running at 50% Capacity
“D” 12% of the time Chiller is running at 25% Capacity
These values will be put into the calculation
“A” = COP or EER at 100% Capacity
“B” = COP or EER at 75% Capacity
“C” = COP or EER at 50% Capacity
“D” = COP or EER at 25% Capacity
AHRI Standard 550 Part Load Condition
Chiller Leaving Water Temperature = 44 o F
Chilled water flow rate 2.4 GPM/ TR
Condenser entering water temperature at 100 % Load = 85 o F
Condenser entering water temperature at 75 % Load = 75 o F
Condenser entering water temperature at 50 % Load = 65 o F
Condenser entering water temperature at 25 % Load = 65 o F
Condenser water flow rate 3 GPM / TR
IPLV  = 0.01(3.285) +0.42(4.466) + 0.45(6.64) +0.12(7.652)
IPLV = 5.81
5.81 IPLV means 1 kW of electric power will give you
5.81 kW cooling output
At 100 % Load COP was 3.289, it means 1 kW of electric power will give 3.289 kW cooling output
For Course Details, WhatsApp 9082044810
कोर्स की जानकारी के लिए WhatsApp 9082044810
Available Course / उपलब्ध पाठ्यक्रम
https://drive.google.com/drive/folder...
E Mail :- [email protected]
Facebook: girishshindehvac
Instagram: girish_shinde_academy
https://www.amazon.in/shop/girishshinde
#girishshinde  #airconditioning  #hvac
2 سال پیش در تاریخ 1401/07/05 منتشر شده است.
4,032 بـار بازدید شده
... بیشتر