SMA Sunny Tripower errorcode 6408 diagnosis. Part 1
9.2 هزار بار بازدید -
5 سال پیش
-
After 6 years of operation,
After 6 years of operation, this SMA Sunny tripower solar inverter stopped working. The errorcode is 6408 and the red LED on the frontpanel is always on. The warranty was 5 years. A new model costs about 2000 euros. The service manual explains that errorcode means "UCE Monitoring". This is a very mysterious description. Suggestion from SMA: Replacement.
Hmm, let's have a look inside first...
(note: if the IGBT on the right is missing, the errorcode is 6438)
Hmm, let's have a look inside first...
(note: if the IGBT on the right is missing, the errorcode is 6438)