Configuring Danfoss VLT Micro FC51 for Process closed loop system using 2-wire Pressure transmitter

DIGICON AUTOMATION
DIGICON AUTOMATION
54.2 هزار بار بازدید - 5 سال پیش - Two wire start stop with
Two wire start stop with process closed loop system using two wire pressure transmitter for Danfoss VLT Micro FC51 Drive || Digicon Automation

Parameters :-

1-00   Configuration Mode                                         [ 3 ] Process
1-01   Motor Control Principle                                   [ 0 ] u/f
1-20   Motor Power                                                     As per motor name plate
1-22   Motor Voltage                                                   As per motor name plate
1-23   Motor Frequency                                              As per motor name plate
1-24   Motor Current                                                   As per motor name plate
1-25   Motor Nominal Speed                                     As per motor name plate
3-03   Max. Reference (Set-Point)                             3.5 Bar
3-10   Preset Reference                                              100
3-15   Reference Resource 1                                     [ 0 ] No function
3-16   Reference Resource 2                                     [ 0 ] No function
3-17   Reference Resource 3                                     [ 0 ] No function
3-41   Ramp 1 Up Time                                              25 sec
3-42   Ramp 1 Down Time                                         40 sec
4-10   Motor Speed Direction                                    [ 0 ] Clockwise
4-14   Motor Speed High Limit                                 50Hz
4-16   Torque Limit Motor Mode                               250%
4-17   Torque Limit Generator Mode                        250%
5-10   Terminal 18 Digital Input                                 [ 8 ] Start
5-11   Terminal 19 Digital Input                                 [ 0 ] No function
5-12   Terminal 27 Digital Input                                 [ 0 ] No function
5-13   Terminal 29 Digital Input                                 [ 0 ] No function
5-15   Terminal 33 Digital Input                                 [ 0 ] No function
6-22   Terminal 60 Low Current                                 4.00 mA
6-23   Terminal 60 High Current                                20.00 mA
6-24   Terminal 60 Low Ref. / Feedback Value        0.0 Bar
6-25   Terminal 60 High Ref. / Feedback Value       10.0 Bar
7-20   Process CL Feedback 1 Resource                  [ 2 ] Analog Input 60
7-33   Process Pi Proportional Gain                          2
7-34   Process Pi Integral Time                                  7